600KW Weichai diesel generator set
Routine maintenance of diesel generator sets:
1. Check the water level and oil level once a day;
2. Clean the outer surface of the unit and the machine room environment once a day.
Monthly maintenance of diesel generator sets:
1. Clean the outer surface of the unit;
2. Check whether the speed regulating rod is flexible and lubricate all connection points;
3. Replace the cooling water, measure the pH value before and after the replacement (normal value is 7.5-9), and keep good measurement records. If necessary, add medicine for treatment (notify the water treatment worker to cooperate);
4. Check the tension of the fan belt and charger belt and adjust if necessary;
5. Cooperate with the electrical emergency power generation test, check whether the instrument readings, temperature and volume are normal when the diesel engine is running, and keep operation records.
Diesel generator set quarterly maintenance:
1. Check the air flow resistance indicator. Clean the air filter when it shows red.
2. Release the diesel water and clean the primary diesel filter;
3. Pay attention to lubrication of the fan pulley and belt tensioner bearings;
4. Check the lubricating oil level of the overspeed mechanical protection device and add oil if it is insufficient;
5. Check the tightness of the main external connection bolts.
Annual maintenance of diesel generator sets:
1. Cooperate with electricians to carry out parallel load operation and check the operation status;
2. Cooperate with electricians to simulate the performance of various safety protection devices;
3. Measure and inspect the axis line and opening, and keep records;
4. Remove the inspection cover and observe the shaft and cylinder;
5. Add chemicals to clean the cooling system (notify the water treatment worker to cooperate);
6. Check the quality of the engine oil and replace it when necessary;
7. Clean the second-stage diesel filter;
8. Clean the oil filter;
600KW Weichai Power Generator Equipment Pictures: